[{"ActivityDescription":"First Review-Fire","DoneBy":"Michael Harris - (425) 229-6577","ActivityDate":"7/29/2026","ActivityStatus":"Approved","RecordDate":"","ActivityNotes":"Separate Permits:\n\n• Required for addition, alteration or revision to:\n           • Electrical Grounding permit\n\nDemo/Construction Safety:\n\n• Demolition and construction shall conform to BFC Chapter 33 an NFPA 241\n\nFIRE APPROVAL CONDITIONS:\n\n1) Per BFC CHAPTERS 9, 50, 57:\n\n-STORAGE AREAS SHALL BE KEEP FREE FROM WEEDS AND EXTRANEOUS COMBUSTIBLE MATERIALS\n\n-OPEN FLAMES AND SMOKING ARE PROHIBITED IN FLAMMABLE OR COMBUSTIBLE LIQUID STORAGE AREAS\n\n-UNIT(S) SHALL BE MARKED AS FOLLOWED:\n      -WHITE LETTERING ON A RED BACKGROUND\n      -LETTERS SHALL BE NOT LESS THAN 3 INCHES IN\n       HEIGHT AND 1/2 INCH IN STROKE\n      -HAZARD IDENTIFICATION AS SPECIFIED IN NFPA 704\n      -\"FLAMMABLE-KEEP FIRE AND FLAME AWAY\"\n      -\"KEEP 50 FEET FROM BUILDINGS\"\n\n-WHEN MOVING UNIT, UNIT SHALL BE EMPTY PRIOR TO MOVEMENT. CALL IN A PRE-CON INSPECTION PRIOR TO MOVING\n\n-UNIT SHALL BE GROUNDED PER MANUFACTURER SHEETS (SEPERATE PERMIT REQUIRED)\n\n-A COPY OF THE INSTRUCTION MANUAL SHALL BE ONSITE WITH THE UNIT AT ALL TIMES\n\n-DISPENSING SHALL NOT BE CONDUCTED WITHIN 25 FEET OF BUILDING OPENINGS, LOT LINES, PUBLIC STREET, PUBLIC ALLEYS OR PUBLIC WAYS.\n\n-A 4-A RATED EXTINGUISHER SHALL BE PLACED NO MORE THEN 75 FEET FROM UNIT\n\n-MOUNTED FIRE EXTINGUISHER SHALL BE PLACED ON ALL FORKLIFTS"}]